When replacing the battery pack in a device, it is important to reset the devices’ battery stats. This will ensure that the new battery level is reported accurately and prevents incorrect low battery messages being shown on the panel. The reset process does not require any use of the control panel.

Please note that the battery stats recalibration is only necessary when replacing a battery on Zerio Plus devices with a version number from 3.00 up to (and including) 3.03.

The version number can be found on a small rectangular white label on the back of the device.

Zerio Plus Battery Stats Recalibration

Battery stats recalibration is not necessary on older Zerio Plus devices which have a blue product label.

Instructions for EDA-D5000, EDA-D6000, EDA-D6030, EDA-R5000, EDA-R6000 and EDA-R6030 Devices

  1. With the device powered off, hold down the reset button on the front of the device and the unit removal button on the back of the device.
  2. Put the power jumper to the ON position and keep both buttons held down for approximately 10 seconds until the second set of beeps is heard, then release the buttons immediately. Do not power the device down, otherwise the battery stats counter will not be reset.
  3. Refit the device to its base.
  4. Wait 15 minutes then reset the panel.

Instructions for EDA-A6000, EDA-A6030, EDA-A6060, EDA-C5000, EDA-T5000 and EDA-T6080 Devices

  1. With the device powered off, hold down the log on button.
  2. Put the power jumper to the ON position and keep the button held down for approximately 10 seconds until the second set of beeps is heard, then release the button immediately.
  3. Refit the device to its base. Do not power the device down, otherwise the battery stats counter will not be reset.
  4. Wait 15 minutes then reset the panel.

If you're interested in this post you may be interested in our wireless fire alarm systems and electro detectors batteries ranges.